Rated characteristics of the Polymer Housed Arrester PA-SL. Ur: 6 kV to 120 kV
Item
|
Type
|
|
PA-SL
|
1
|
Arrester class according
IEC 60099-4:2014
|
|
SL
Station Low
|
2
|
Rated frequency
|
Hz
|
48 - 62 Hz
|
3
|
Rated voltage
|
kV
|
6 - 120
|
4
|
Continuous operating voltage
|
kV
|
4,8 - 96
|
5
|
Nominal discharge current In 8/20 μs
|
kA
|
10
|
6
|
High current impulse Ihc 4/10 μs
|
kA
|
100
|
7
|
Charge Transfer Rating, Qrs
|
C
|
1,2
|
8
|
Thermal energy rating, Wth
|
kJ/kV
|
6,0 (Ur)
|
9
|
Short circuit rating Is 50 Hz
|
kA
|
65
|
List of test reports of the surge arresters type PA-SL
Item
|
Description
|
Standard clause
|
Protocol number
|
Testing laboratory
|
1
|
Test to verify the repetitive charge transfer rating
|
IEC 60099-4 cl. 8.5 & 10.8.5
|
B8000389
|
CESI S.p.A.,
Milan, Italy
|
2
|
Residual voltage test
|
IEC 60099-4 cl. 8.3 & 10.8.3
|
B8000858
|
CESI S.p.A.,
Milan, Italy
|
3
|
Heat dissipation test
|
IEC 60099-4 cl. 10.8.6 & Annex B
|
B8001241
|
CESI S.p.A.,
Milan, Italy
|
4
|
Operating duty test
|
IEC 60099-4 cl. 8.7 & 10.8.7
|
B8006271
|
CESI S.p.A.,
Milan, Italy
|
5
|
Power frequency voltage versus time test
|
IEC 60099-4 cl. 8.8 & 10.8.8
|
B8006272
|
CESI S.p.A.,
Milan, Italy
|
6
|
Test to verify long thermal stability under continuous operating voltage (1000 h)
|
IEC 60099-4 cl. 8.4 & 10.8.4
|
B8004676
|
CESI S.p.A.,
Milan, Italy
|
7
|
Insulation withstand test of the arrester housing
|
IEC 60099-4 cl. 8.2 & 10.8.2
|
B7018646-1
|
CESI S.p.A.,
Milan, Italy
|
8
|
Short circuit tests
(Is = 20 kA)
(Is = 65 kA)
|
IEC 60099-4 cl. 8.10 & 10.8.10
|
B7011173
|
CESI S.p.A.,
Milan, Italy
|
08-047
|
ZKU,
Praha, Czech Republic
|
9
|
Short circuit tests
|
IEE C62.11-2012 cl.8.18.2.4
|
B7011174
|
CESI S.p.A.,
Milan, Italy
|
Rated characteristics of the Polymer Housed Arrester PA-DM, Ur: 3 kV to 54 kV.
Item
|
Type
|
|
PA-DM
|
1
|
Arrester class according
IEC 60099-4:2014
|
|
DH
(Distribution high)
|
2
|
Rated frequency
|
Hz
|
48 - 62 Hz
|
3
|
Rated voltage
|
kV
|
3 – 54
|
4
|
Continuous operating voltage
|
kV
|
2,4 – 43.2
|
5
|
Nominal discharge current In 8/20 μs
|
kA
|
10
|
6
|
High current impulse Ihc 4/10 μs
|
kA
|
100
|
7
|
Charge Transfer Rating, Qrs
|
C
|
0,4
|
8
|
Thermal Charge Transfer Rating, Qth
|
C
|
1,1
|
|
Short circuit rating Is 50 Hz
|
kA
|
20
|
List of test reports of the surge arresters type PA-DM.
Item
|
Description
|
Standard clause
|
Protocol number
|
Testing laboratory
|
1
|
Test to verify the repetitive charge transfer rating
|
IEC 60099-4 cl. 8.5 & 10.8.5
|
B7018719
|
CESI S.p.A.,
Milan, Italy
|
2
|
Residual voltage test
|
IEC 60099-4 cl. 8.3 & 10.8.3
|
B7019592
|
CESI S.p.A.,
Milan, Italy
|
3
|
Heat dissipation test
|
IEC 60099-4 cl. 10.8.6 & Annex B
|
B7018623
|
CESI S.p.A.,
Milan, Italy
|
4
|
Operating duty test
|
IEC 60099-4 cl. 8.7 & 10.8.7
|
B7019962
|
CESI S.p.A.,
Milan, Italy
|
5
|
Power frequency voltage versus time test
|
IEC 60099-4 cl. 8.8 & 10.8.8
|
B7020147
|
CESI S.p.A.,
Milan, Italy
|
6
|
Test to verify long thermal stability under continuous operating voltage (1000 h)
|
IEC 60099-4 cl. 8.4 & 10.8.4
|
B8001026
|
CESI S.p.A.,
Milan, Italy
|
7
|
Insulation withstand test of the arrester housing
|
IEC 60099-4 cl. 8.2 & 10.8.2
|
B7018645
|
CESI S.p.A.,
Milan, Italy
|
8
|
Short circuit tests
|
IEC 60099-4 cl. 8.10 & 10.8.10
|
B6022563
|
CESI S.p.A.,
Milan, Italy
|
9
|
Short circuit tests
|
IEE C62.11-2012 cl.8.18.2.4
|
B6022564
|
CESI S.p.A.,
Milan, Italy
|
Rated characteristics of the Polymer Housed Arrester PA-DH, Ur: 3 kV to 54 kV.
Item
|
Type
|
|
PA-DH
|
1
|
Arrester class according
IEC 60099-4:2014
|
|
DH
(Distribution high)
|
2
|
Rated frequency
|
Hz
|
48 - 62 Hz
|
3
|
Rated voltage
|
kV
|
3 – 54
|
4
|
Continuous operating voltage
|
kV
|
2,4 – 43.2
|
5
|
Nominal discharge current In 8/20 μs
|
kA
|
10
|
6
|
High current impulse Ihc 4/10 μs
|
kA
|
100
|
7
|
Charge Transfer Rating, Qrs
|
C
|
0,5
|
8
|
Thermal Charge Transfer Rating, Qth
|
C
|
1,1
|
|
Short circuit rating Is 50 Hz
|
kA
|
20
|
List of test reports of the surge arresters type PA-DH.
Item
|
Description
|
Standard clause
|
Protocol number
|
Testing laboratory
|
1
|
Test to verify the repetitive charge transfer rating
|
IEC 60099-4 cl. 8.5 & 10.8.5
|
B7023946
|
CESI S.p.A.,
Milan, Italy
|
2
|
Residual voltage test
|
IEC 60099-4 cl. 8.3 & 10.8.3
|
B7023620
|
CESI S.p.A.,
Milan, Italy
|
3
|
Heat dissipation test
|
IEC 60099-4 cl. 10.8.6 & Annex B
|
B7023423
|
CESI S.p.A.,
Milan, Italy
|
4
|
Operating duty test
|
IEC 60099-4 cl. 8.7 & 10.8.7
|
B7024361
|
CESI S.p.A.,
Milan, Italy
|
5
|
Power frequency voltage versus time test
|
IEC 60099-4 cl. 8.8 & 10.8.8
|
B7024813
|
CESI S.p.A.,
Milan, Italy
|
6
|
Test to verify long thermal stability under continuous operating voltage (1000 h)
|
IEC 60099-4 cl. 8.4 & 10.8.4
|
B8003845
|
CESI S.p.A.,
Milan, Italy
|
7
|
Insulation withstand test of the arrester housing
|
IEC 60099-4 cl. 8.2 & 10.8.2
|
B7018645
|
CESI S.p.A.,
Milan, Italy
|
8
|
Short circuit tests
|
IEC 60099-4 cl. 8.10 & 10.8.10
|
B6020613
|
CESI S.p.A.,
Milan, Italy
|
9
|
Short circuit tests
|
IEE C62.11-2012 cl.8.18.2.4
|
B6020612
|
CESI S.p.A.,
Milan, Italy
|
Rated characteristics of the Polymer Housed Arrester PA-SM, Ur: 6 kV to 228 kV.
Item
|
Type
|
|
PA-SM
|
1
|
Arrester class according
IEC 60099-4:2014
|
|
Station Medium;
SM
|
2
|
Rated frequency
|
Hz
|
48 - 62 Hz
|
3
|
Rated voltage
|
kV
|
6,0 - 228
|
4
|
Continuous operating voltage
|
kV
|
4,8 – 182,4
|
5
|
Nominal discharge current In 8/20 μs
|
kA
|
10
|
6
|
High current impulse Ihc 4/10 μs
|
kA
|
100
|
7
|
Charge Transfer Rating, Qrs
|
C
|
2,0
|
8
|
Thermal energy rating, Wth
|
kJ/kV
|
9,0 (Ur)
|
9
|
Short circuit rating Is 50 Hz
|
kA
|
65
|
List of test reports of the surge arresters type PA-SM.
Item
|
Description
|
Standard clause
|
Protocol number
|
Testing laboratory
|
1
|
Test to verify the repetitive charge transfer rating
|
IEC 60099-4 cl. 8.5 & 10.8.5
|
B8004364
|
CESI S.p.A.,
Milan, Italy
|
2
|
Residual voltage test
|
IEC 60099-4 cl. 8.3 & 10.8.3
|
B8005438
|
CESI S.p.A.,
Milan, Italy
|
3
|
Heat dissipation test
|
IEC 60099-4 cl. 10.8.6 & Annex B
|
B8004964
|
CESI S.p.A.,
Milan, Italy
|
4
|
Operating duty test
|
IEC 60099-4 cl. 8.7 & 10.8.7
|
B8005341
|
CESI S.p.A.,
Milan, Italy
|
5
|
Power frequency voltage versus time test
|
IEC 60099-4 cl. 8.8 & 10.8.8
|
B8005342
|
CESI S.p.A.,
Milan, Italy
|
6
|
Test to verify long thermal stability under continuous operating voltage (1000 h)
|
IEC 60099-4 cl. 8.4 & 10.8.4
|
B8007469
|
CESI S.p.A.,
Milan, Italy
|
7
|
Insulation withstand test of the arrester housing
|
IEC 60099-4 cl. 8.2 & 10.8.2
|
B8001593
|
CESI S.p.A.,
Milan, Italy
|
8
|
Short circuit tests
|
IEC 60099-4 cl. 8.10 & 10.8.10
|
08-047
|
ZKU,